EDM SolutionsMunicipal & Utility Tender Portal
← Eskom TEAP register
Accepted product recordHV PLANT - Cable Systems

RING MAIN UNIT * NON-EXTENSIBLE * INDOOR * CONSISTING OF : 2 x RING-SWITCHES, 1 x TEE-OFF SWITCH-FUSE COMBINATION * NOMINAL VOLTAGE : 11kV * RATED NORMAL CURRENT (RING-SWITCH) : 630A * RATED SHORT-TIME CURRENT : 20kA (3 SEC.) * ALL BUSHINGS TO BE 630A TYPE C TO EN50181 WITH M16 x 2 THREAD * SUPPLIED WITH : EARTH FAULT INDICATOR FITTED IN LEFT CABLE TERMINATION ENCLOSURE, AIR-FILLED CABLE TERMINATION ENCLOSURES WITH CABLE SUPPORT, RAISING BASE (MOUNTING PEDESTAL) WITH 3 x CABLE SUPPORT CLAMPS (SEE D-DT-8019) AND REMOVABLE FRONT SECTION, IAC AFLR 20kA 0.5s * RAISING BASE GLAND PLATE TO BE FITTED WITH 3 x RUBBER GROMMETS (SEE D-DT-8027) * NOT TO BE SUPPLIED WITH FUSE-LINKS * COASTAL APPLICATION * ESKOM DRAWING No. D-DT-8060 *

RMU 11kV 630A 2R-1F N/EXT CSTL I/D

Official register information

Eskom SAP / Material Number
235397
Manufacturer
ABB
Product code
SafePlus, CCF
Centre of Excellence
HV PLANT - Cable Systems
Material group
RING MAIN UNITS (RMUs)
D-DT drawing
D-DT-8060
Product drawing reference
0235397 (CCF12kV indoor)
Technical specification reference
240-56030406 Rev 2
TEC reference
240-133693752 Rev 3
Enquiry number
DX896
Source of listing
Eskom tender bulletin
Listing date
2024-05-01

Source comment

Refer to the following documents for more information: 1. 240-170000811 Rev3. 1: Technical evaluation report for RMUs for DX 896. 2. 240-170000892 Rev 1: Factory sample evaluation report for free standing RMUs (DX896). 3. 240-170001029: Technical bulletiin for Eskom national contract for free standing RMUs for DX 896.